Networking devices and products to assist in integration to other systems. |
| |
|


|
DIR-TX8 - Infra-red Transmitter
• 12V DC 50mA, supplied from DyNet network
• 8 independent, individually controllable outputs
• 4 x 3.5mm stereo jack connector, accepts stereo & mono plugs
• 1 x IR input, used for learning & saving unknown IR codes
• 1 x RS485 DyNet port
• 1 x AUX programmable dry contact input
• Programmable logic controller
• Dimensions: H 30mm x W 80mm x D 150mm
• Packed weight 0.15kg
• DIR-EM2 supplied separately
|
|

|
DDMIDC8 - Dry Contact/Voltage Input Interface
• 8 x Opto Isolated inputs, each configurable to Dry Contact or 0-24V AC/DC inputs
• 4 x 0-10V DC analogue non-isolated inputs
• LED status indicators for each opto isolated input
• Programmable logic controller
• Powered from the DyNet network
• RS485 DyNet port
• DIN Rail enclosure, 6 units wide
• Can be mounted on DIN rail, also has provision for screw fixing to a wall without the use of DIN rail
• Dimensions H 86mm x W 105mm x D 58mm
• Packed weight 0.324kg
|
|

|
DDNG485 - Network Gateway
• Powered from the network, no mains supply required
• 2 x RS485 DyNet serial ports
• Optical Isolation between ports
• Programmable message filtering
• Programmable logic controller
• DIN Rail enclosure, 6 units wide
• Can be mounted on DIN rail, also has provision for screw fixing to a wall without the use of DIN rail
• Dimensions H 86mm x W 105mm x D 58mm
• Packed weight 0.324kg
|
|
|
DNG485 - Network Gateway
• 230V 50/60Hz single phase at <0.1A
• 2 x RS485 DyNet serial ports
• 3.75KV RMS Optical Isolation between ports
• Packet filtering
• DyNet to DyNet II translation
• Programmable logic controller
• DMX512 Receive: 64 channels
• DMX512 Transmit: 64 channels
• Dimensions H 320mm x W 225mm x D 75mm
• Packed weight 3.1kg
|
|
|
|
|

|
DDNI-LON - DyNet to LON Interface
• DyNet to LON interface
• 1 x RS485 DyNet Serial Port
• 1 x TP/FTT10A twisted pair LONWorks port
• Supports 63 SNVTs
• Dimensions: H 86mm x W 105mm x D 70mm
• Packed weight 0.6kg
|
|

|
DNG232 - RS232 Gateway
• DyNet to RS232 Gateway
• 1 x RS485 DyNet serial port
• 1 x RS232 serial port
• RS232 port can be programmed to transmit custom data
• Pre programmed "Plain English" text interpreter mode
• Pre programmed Remote Access Modem mode
• RS232 Baud rate: 600 - 460800
• RS232 Max packet length: 254 bytes
• Dimensions: H 30mm x W 80mm x D 150mm
• Packed weight 0.15kg
|
|

|
DTK502 - Dry Contact Inputs
• Designed to fit into third party devices to allow operation on a DyNet network.
• 4 dry contact inputs
• Powered from the DyNet network
• Small enough to fit into 3rd party PIR motion sensors
• Firmware supports special "motion detector" mode
• 1 x RS485 DyNet serial port
• Dimensions H 19mm x W 45mm x D 19mm
• Weight 15.5 grams
|
|

|
DTK932V7 - Network Bridge
• 230V single phase & neutral supply at 0.25A
• 2 x RS485 serial ports, supports DyNet & DMX512 TX
• Optical Isolation between ports
• Programmable message filtering
• Programmable logic controller
• DMX512 Transmit - 512 Channels
• Memory: 8Kb EEPROM, 512Kb DRAM, 1024Kb FLASH
• Dimensions H 320mm x W 225mm x D 70mm
• Packed weight 3.1kg
|
| |
|
| |
|
| |
|
| |
|
| |
|
| |
|
| |
|
| |
|